OVERVIEW
This Liebert GXT3 10kVA unit offers a flexible solution for protecting rack-mount equipment, including VoIP and PoE.
Especially designed for use with the new generation of high power switches, this compact UPS system packs 10kVA (9kW) of power into a 6U rack/tower package with flexible output voltage and bundled output distribution and maintenance bypass.
The UPS includes built-in user-replaceable batteries for up to 3 minutes of runtime at full load.
24 Months Warranty
SPECIFICATIONS
Model Number GXT3-10000RT230
Rating(VA/W) 10000VA/9000W
Physical Dimensions
Unit: WxDxH(mm) 430x577x261
Shipping: WxDxH(mm) 515x717x570
Weight
Unit (kg)
80
Shipping (kg)
82
Input AC Parameters
Operating Frequency 50 or 60Hz Nominal (factory Default=50)
Factory Default 230VAC
User Configurable 220/230/240VAC
Operating Voltage Range (w/o battery operation) 176-280VAC
Maximum Allowable 280VAC
Input Frequency (w/o battery operation) 40 to 70Hz
Input Power Connection PD2-CE10HDWRMBS Standard
Output AC Parameters
Factory Default 230VAC
Output Connections PD2-CE10HDWRMBS Standard
Frequency 50 or 60Hz Nominal
Waveform Sinewave
Main Mode Overload >200% for 5 cycles; 151 to 200% for 1 seconds; 1331 to 150% 10 seconds; 105 to 130% 1 minute
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity 20 x 12V
Recharge Time (internal batteries) 3 hrs to 90% capacity after full discharge into 100% load
Bypass Protection Limits
Disable Bypass Operation If input voltage exceeds ± 15% of the nominal voltage
Re-Enable Bypass Operation If input voltage returns to within ± 10% of the nominal voltage
Disable Bypass Operation When the input frquency prevents synchronous operation
Environmental
Operating Temperature (°C) 0 to 40
Storage Temperature (°C) -15 to 50
Relative Humidity 0 to 95%; non-condensing
Operating Elevation Up to 1000m at 30°C without derating
Audible Noise < 55dBA at 1 meter from the rear; < 50 dBA at 1 meter from the front or sides
Agency Approvals
Safety IEC62040-1:2008 version
EMI/EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2-Table 6)
ESD EN61000-4-2,Level 4, Criteria A
Radiated Susceptibiltiy EN61000-4-3,Level 3, Criteria A
Electrical Fast Transient EN61000-4-4,Level 4, Criteria A
Surge Immunity EN61000-4-5,Level 3, Criteria A
Transportation ISTA Procedure 1A